Belden 88641 Cable Equivalent, FEP-TFE, Price $290/1000 ft.
Detailed Specifications and Technical Data

Description: 24 AWG stranded (7x32) TC conductors, FEP insulation, twisted one pair, overall foil shield (100% coverage), 24 AWG stranded TC drain wire, FEP jacket - Red. Plenum Rated CMP.

Physical Characteristics:
BELDEN 88641 CABLE
CONDUCTOR:
PRICE $290/1000 ft.

Number of Pairs 1
Total Number of Conductors 2
AWG 24
Stranding 7x32
Conductor Material TC - Tinned Copper
BELDEN 88641 CABLE INSULATION:
Insulation Material FEP - Fluorinated Ethylene Propylene
Nom. Insulation Wall Thickness .006 in.
Lay Length 2.0 in.
Twists/ft. 6
Pair Color Code Chart:
Number: 1

Black & Red
BELDEN 88641 OVERALL CABLING:
Overall Cabling Separator Material Polyester tape
Overall Cabling Separator Thickness 0.001 in.
BELDEN 88641 CABLE OUTER SHIELD:
Outer Shield Type Tape
Outer Shield Material Aluminum Foil-Polyester Tape
Outer Shield % Coverage 100%
BELDEN 88641 CABLE OUTER SHIELD DRAIN WIRE:
Outer Shield Drain Wire AWG 24
Outer Shield Drain Wire Stranding Stranded
Outer Shield Drain Wire Conductor Material TC - Tinned Copper
BELDEN 88641 CABLE OUTER JACKET:
Outer Jacket Material FEP - Fluorinated Ethylene Propylene
Outer Jacket Nominal Wall Thickness .014 in.
BELDEN 88641 CABLE OVERALL NOMINAL DIAMETER:
Overall Nominal Diameter .106 in.
BELDEN 88641 CABLE MECHANICAL CHARACTERISTICS:
Operating Temperature Range -70°C To +200°C
Bulk Cable Weight 9.3 lbs/1000 ft.
Max. Recommended Pulling Tension 16 lbs.
Min. Bend Radius (Install) 1.1 in.
APPLICABLE SPECIFICATIONS AND AGENCY COMPLIANCE:
BELDEN 88641 CABLE APPLICABLE STANDARDS:
NEC/(UL) Specification CMP
CEC/C(UL) Specification CMP
EU CE Mark (Y/N) Yes
EU RoHS Compliant (Y/N) Yes
BELDEN 88641 CABLE FLAME TEST:
UL Flame Test NFPA 262
C(UL) Flame Test FT6
BELDEN 88641 CABLE SUITABILITY:
Suitability - Indoor Yes
Suitability - Outdoor Yes
Suitability - Burial Yes
Oil Resistance Yes
BELDEN 88641 CABLE ELECTRICAL CHARACTERISTICS:
Nom. Characteristic Impedance 24 Ohms
Nom. Inductance .17 £gH/ft
Nom. Capacitance Cond. to Cond. @ 1 KHz 31 pF/ft
Nom. Cap. Cond. to Other Cond. & Shield @ 1 KHz 59 pF/ft
Nominal Velocity of Propagation --
Nominal Delay --
Nom. Conductor DC Resistance @ 20°C 24 Ohms/1000 ft
Nom. Outer Shield DC Resistance @ 20°C 17 Ohms/1000 ft
Max. Operating Voltage - UL 300 V RMS
Max. Recommended Current 2.2 Amps per conductor @ 25°C
NOTES: For use in indoor plenum environments but also suitable for outdoor and underground applications.

PUT-UPS AND COLORS - ALL SPOOLS ARE CONTINUOUS LENGTHS
88641 Cable
$290/1000 ft.
Put-Up (ft.) Ship Weight Jacket Color
88641 Cable 1000 9 lbs. RED
88641 Cable 2000 18 lbs. RED
88641 Cable 2500 23 lbs. RED
88641 Cable 3000 27 lbs. RED
88641 Cable 5000 45 lbs. RED

PlenumCable2.com is a division of WorldWideWire.com.