Belden 89418 Cable Equivalent, Teflon®, Price $710/1000 ft.
Detailed Specifications and Technical Data
Description: 18 AWG stranded (19x30) TC conductors, Teflon®, FEP insulation, four conductor, overall foil shield (100% coverage), 20 AWG stranded TC drain wire, FEP jacket - Red. Plenum Rated CMP.
Physical Characteristics:
BELDEN 89418 CABLE CONDUCTOR:
PRICE $710/1000 ft.
|
| Number of Pairs |
-- |
| Total Number of Conductors |
4 |
| AWG |
18 |
| Stranding |
19x30 |
| Conductor Material |
TC - Tinned Copper |
BELDEN 89418 CABLE INSULATION:
|
| Insulation Material |
FEP - Fluorinated Ethylene Propylene |
| Nom. Insulation Wall Thickness |
.007 in. |
| Lay Length |
-- |
| Twists/ft. |
-- |
Pair Color Code Chart:
Number: 1
|
Black, White, Red, Green
|
BELDEN 89418 OVERALL CABLING:
|
| Overall Cabling Separator Material |
Polyester tape |
| Overall Cabling Separator Thickness |
0.001 in. |
BELDEN 89418 CABLE OUTER SHIELD:
|
| Outer Shield Type |
Tape |
| Outer Shield Material |
Aluminum Foil-Polyester Tape |
| Outer Shield % Coverage |
100% |
BELDEN 89418 CABLE OUTER SHIELD DRAIN WIRE:
|
| Outer Shield Drain Wire AWG |
20 |
| Outer Shield Drain Wire Stranding |
Stranded |
| Outer Shield Drain Wire Conductor Material |
TC - Tinned Copper |
BELDEN 89418 CABLE OUTER JACKET:
|
| Outer Jacket Material |
FEP - Fluorinated Ethylene Propylene |
| Outer Jacket Nominal Wall Thickness |
.014 in. |
BELDEN 89418 CABLE OVERALL NOMINAL DIAMETER:
|
| Overall Nominal Diameter |
.177 in. |
BELDEN 89418 CABLE MECHANICAL CHARACTERISTICS:
|
| Operating Temperature Range |
-70°C To +200°C |
| Bulk Cable Weight |
38 lbs/1000 ft. |
| Max. Recommended Pulling Tension |
114 lbs. |
| Min. Bend Radius (Install) |
1.75 in. |
| APPLICABLE SPECIFICATIONS AND AGENCY COMPLIANCE: |
BELDEN 89418 CABLE APPLICABLE STANDARDS:
|
| NEC/(UL) Specification |
CMP |
| CEC/C(UL) Specification |
CMP |
| EU CE Mark (Y/N) |
Yes |
| EU RoHS Compliant (Y/N) |
Yes |
BELDEN 89418 CABLE FLAME TEST:
|
| UL Flame Test |
NFPA 262 |
| C(UL) Flame Test |
FT6 |
BELDEN 89418 CABLE SUITABILITY:
|
| Suitability - Indoor |
Yes |
| Suitability - Outdoor |
Yes |
| Suitability - Burial |
Yes |
| Oil Resistance |
Yes |
BELDEN 89418 CABLE ELECTRICAL CHARACTERISTICS:
|
| Nom. Characteristic Impedance |
29 Ohms |
| Nom. Inductance |
.15 £gH/ft |
| Nom. Capacitance Cond. to Cond. @ 1 KHz |
30 pF/ft |
| Nom. Cap. Cond. to Other Cond. & Shield @ 1 KHz |
57 pF/ft |
| Nominal Velocity of Propagation |
-- |
| Nominal Delay |
-- |
| Nom. Conductor DC Resistance @ 20°C |
6.4 Ohms/1000 ft |
| Nom. Outer Shield DC Resistance @ 20°C |
7.9 Ohms/1000 ft |
| Max. Operating Voltage - UL |
300 V RMS |
| Max. Recommended Current |
4.3 Amps per conductor @ 25°C |
| NOTES: |
For use in indoor plenum environments but also suitable for outdoor and underground applications. |